Generator sizing, fuel usage, and runtime
How much fuel will my backup generator burn, and how long will it run?
Work it out from energy, not tank size: fuel = generator size × load × hours × burn rate. The site's generator calculator uses 0.078 gallons per kWh for diesel, then adds a 10% planning margin — 0.0858 gal/kWh in mild weather at sea level. So a 20 kW generator carrying a realistic 35% load (the calculator's Standard Home Backup preset) burns 0.60 gallons an hour: about 4.8 gallons for an 8-hour outage, costing $18.26 at the calculator's $3.80/gal diesel price. A 12-hour winter storm on a 30 kW unit at 45% load takes about 14.0 gallons.
The formula: it is the load that drinks, not the badge on the generator
A generator's fuel use follows the energy it actually delivers. The calculator multiplies four things: rated size in kW, load factor (the share of that rating you are really using), hours of runtime, and a burn rate of 0.078 gallons per kWh for diesel at 25 °C and sea level. It then adds a 10% safety margin, because planning an outage to the last cup of fuel is how freezers thaw.
That load factor is where estimates usually go wrong. A 20 kW standby unit rarely carries 20 kW of house. The calculator's own presets put a standard home's essential loads at 35% — fridge, lights, furnace blower, a few outlets — not the 75–100% people picture when they size a fuel store.
Worked examples, straight from the calculator's presets
These are three of the presets built into the fuel calculator, with its temperature and altitude adjustments applied:
| Scenario | Generator | Load | Runtime | Fuel needed | Per hour | Fuel cost |
|---|---|---|---|---|---|---|
| Standard home backup (essentials) | 20 kW | 35% | 8 h | 4.8 gal | 0.60 gal/h | $18.26 |
| Winter storm (heating priority, −5 °C) | 30 kW | 45% | 12 h | 14.0 gal | 1.17 gal/h | $53.35 |
| Extended outage (minimal comfort) | 40 kW | 25% | 24 h | 20.7 gal | 0.86 gal/h | $78.72 |
- Halve the load and you halve the fuel — in the calculator's tests, a unit at 50% load burns exactly half of the same unit at full load over the same hours.
- Runtime is linear too: the hourly burn does not change, only the total. If you know gallons per hour, tank runtime is just usable gallons ÷ that rate.
- Hourly burn follows the power actually delivered, not the badge: the 40 kW unit at 25% load delivers 10 kW, so at 0.86 gal/h it burns less per hour than the 30 kW winter-storm unit delivering 13.5 kW (1.17 gal/h) — but more than the 20 kW standard-home unit delivering 7 kW (0.60 gal/h). Right-sizing the load list beats obsessing over the rating.
Cold, altitude, and biodiesel each take a cut
The base rate assumes a mild day at sea level. The calculator adjusts it three ways, and the adjustments multiply together:
- Cold: below 0 °C, consumption rises 0.2% for every degree — a −10 °C night costs about 2% more fuel, and −30 °C is the calculator's tested extreme.
- Heat: above 30 °C, it rises 0.1% per degree.
- Altitude: +3% per 1,000 m. The high-altitude preset (2,000 m) carries a 6% penalty before anything else is counted.
- Biodiesel: +7% consumption versus diesel in the calculator, and priced at $4.20/gal against diesel's $3.80 — it costs more per gallon and burns more gallons.
So how long will a tank last?
Take the fuel you actually have, divide by the hourly burn for your real load, and stop there — that is the honest runtime. For the standard-home example above, 10 gallons on hand ÷ 0.60 gal/h is about 16 hours of essential-loads cover. The trap is dividing by the wrong rate. Use the full-load burn rate for a generator that will actually loaf along at a third load and the answer comes out far shorter than the runtime you really have — safe, but it sends you out to buy and store fuel you did not need. Use a light-load rate for a house that will actually run near full load and the error flips: the tank empties before your estimate says it should, mid-outage. The rate has to match the load you will really carry.
Run your own numbers
Put your generator size, your realistic load, and your weather into the calculator and it returns the gallons, the hourly burn, and the cost — including the 10% margin — before the outage does the arithmetic for you.